1. Metropolitan Hotel
Sector: Hospitality
Project Overview
Metropolitan Hotel is included in Buraq’s hospitality project portfolio. The project can be presented as part
of the company’s experience supporting hotel and hospitality environments, where HVAC and
building-service systems must be coordinated with operational requirements and occupant comfort.
Buraq Electro Mechanical LLC provides HVAC and electromechanical services for hospitality facilities,
including installation, air distribution, equipment integration, testing and maintenance. The reviewed source
material identifies Metropolitan Hotel as a project/client reference but does not provide sufficient verified
technical detail to specify the exact completed systems, quantities or project scope.

2. Le Royal Méridien, Abu Dhabi
Sector: Hospitality / Hotel
Project Overview
At Le Royal Méridien Abu Dhabi, Buraq Electromechanical Repairs Works LLC carried out mechanical
restoration and precision laser alignment of critical high-flow centrifugal chilled water pumps serving the
HVAC primary/secondary loop. The documented project addressed mechanical seal leakage, bearing
wear, impeller cavitation and shaft runout while maintaining the operational requirements of the hotel.
The documented scope included site diagnostics, safe isolation, pump demounting and workshop
overhaul, impeller restoration and dynamic balancing, bearing and seal replacement, precision machining,
site reinstallation and laser shaft alignment. The pump casing was hydrostatically tested at 10 bar before
recommissioning, with operational vibration and thermal checks used to verify system performance.

3. Capital Centre Arjaan by Rotana, Abu Dhabi
Sector: Hospitality / Hotel
Project Overview
Capital Centre Arjaan by Rotana is documented through two hospitality mechanical projects involving
domestic hot water balancing and non-return valve replacement. The works addressed hydraulic
performance within the hotel’s domestic water and HVAC hydronic systems, with the execution planned
around an occupied hospitality environment and continuity of guest services.
The documented works included supply and installation of Double Regulating Valves for domestic hot
water return risers, differential-pressure measurement, proportional balancing, valve calibration and
thermal verification. A separate NRV project included isolation and LOTO, removal of worn valves,
installation of PN16/PN25 dual-plate or spring-loaded NRVs, flange alignment, 12-bar hydrostatic pressure
testing, backflow verification and recommissioning.

4. Grand Millennium Al Wahda, Abu Dhabi
Sector: Hospitality / Hotel
Project Overview
Buraq Electromechanical Repairs Works LLC documented an emergency fire pump overhaul project at
Grand Millennium Al Wahda, Abu Dhabi. The project involved the hotel’s electric and diesel engine-driven
split-case centrifugal fire pumps together with the jockey pump, with the work focused on restoring
mechanical condition and fire-protection system performance.
The documented scope included system isolation and safety procedures, mechanical teardown, impeller
inspection and dynamic balancing, shaft-sleeve machining, seal and bearing replacement, reassembly and
precision laser shaft alignment. The pump casing underwent a 16-bar hydrostatic test, followed by NFPA
20 flow testing at churn, rated flow and 150% peak capacity, with recommissioning associated with Abu
Dhabi Civil Defence requirements.

5. Mediclinic City Hospital
Sector: Healthcare
Project Overview
Mediclinic City Hospital is included in Buraq’s healthcare project references. The available project/product
records specifically identify Galvanized Iron (GI) ductwork for the project, establishing documented
experience with HVAC air-distribution ductwork in a healthcare facility.
Buraq’s documented ductwork capability covers duct fabrication and installation, fittings, supports,
insulation, sealing, dampers, grilles, diffusers and associated air-distribution components. For Mediclinic
City Hospital, the reviewed source confirms the GI ductwork reference but does not provide sufficient
project-specific information to state quantities, installation dates or additional completed systems.

6. Danat Al Emarat Hospital for Women & Children
Sector: Healthcare
Project Overview
Danat Al Emarat Hospital for Women & Children is included in Buraq’s healthcare project references. The
available project/product records specifically identify Galvanized Iron (GI) ductwork for the project,
demonstrating documented involvement in HVAC air-distribution works for a healthcare environment.
Buraq provides ductwork and ventilation services covering engineering coordination, fabrication,
installation, insulation, sealing, supports, dampers and air-distribution components. For Danat Al Emarat
Hospital, the reviewed source confirms the GI ductwork reference but does not provide sufficient
project-specific information to state quantities, dates or additional completed systems.